Core Geometry
Nominal conductor diameterd2.8[mm]
Nominal conductor cross sectionnccs6[mm2]
Core Resistance single conductor (Corrected for IEC 60287)
Resistance copper wireRCU2972.5[mΩ/km]
Voltage drop copper wireV(RCU)2.97[volt/km]
Resistance Aluminium wireRAL4702.9[mΩ/km]
Voltage drop Aluminium wireV(RAL)4.7[volt/km]








Core figure a
Cable-InductanceLcable0.892[mH/km]
Cable-ReactanceXcable280.113[mΩ/km]
Cable-CapacitanceCcable14.049[nF/km]
Cable-Impedance(50Hz) CUZcable2985.69[mΩ/km]
Cable-Impedance(50Hz) ALZcable4711.224[mΩ/km]
Voltage drop(50Hz) CUVcable2.986[V/km]
Voltage drop(50Hz) ALVcable4.711[V/km]
Phase shift(50Hz) CUphasecable0.607992[Degrees/km]
Phase shift(50Hz) ALphasecable0.962[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.102[mA]




Core figure b
Cable-InductanceLcable0.892[mH/km]
Cable-ReactanceXcable280.113[mΩ/km]
Cable-CapacitanceCcable14.057[nF/km]
Cable-Impedance(50Hz) CUZcable2985.69[mΩ/km]
Cable-Impedance(50Hz) ALZcable4711.224[mΩ/km]
Voltage drop(50Hz) CUVcable2.986[V/km]
Voltage drop(50Hz) ALVcable4.711[V/km]
Phase shift(50Hz) CUphasecable0.607992[Degrees/km]
Phase shift(50Hz) ALphasecable0.962[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.102[mA]




Core figure c
Cable-InductanceLcable1.095[mH/km]
Cable-ReactanceXcable343.992[mΩ/km]
Cable-CapacitanceCcable11.178[nF/km]
Cable-Impedance(50Hz) CUZcable2992.359[mΩ/km]
Cable-Impedance(50Hz) ALZcable4715.454[mΩ/km]
Voltage drop(50Hz) CUVcable2.992[V/km]
Voltage drop(50Hz) ALVcable4.715[V/km]
Phase shift(50Hz) CUphasecable0.495095[Degrees/km]
Phase shift(50Hz) ALphasecable0.783[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.081[mA]




Core figure d
Cable-InductanceLcable0.446[mH/km]
Cable-ReactanceXcable140.057[mΩ/km]
Cable-CapacitanceCcable28.097[nF/km]
Cable-Impedance(50Hz) CUZcable2975.819[mΩ/km]
Cable-Impedance(50Hz) ALZcable4704.975[mΩ/km]
Voltage drop(50Hz) CUVcable2.976[V/km]
Voltage drop(50Hz) ALVcable4.705[V/km]
Phase shift(50Hz) CUphasecable1.215846[Degrees/km]
Phase shift(50Hz) ALphasecable1.923[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.203[mA]




Core figure e
Cable-InductanceLcable0.629[mH/km]
Cable-ReactanceXcable197.629[mΩ/km]
Cable-CapacitanceCcable76.821[nF/km]
Cable-Impedance(50Hz) CUZcable2979.084[mΩ/km]
Cable-Impedance(50Hz) ALZcable4707.04[mΩ/km]
Voltage drop(50Hz) CUVcable2.979[V/km]
Voltage drop(50Hz) ALVcable4.707[V/km]
Phase shift(50Hz) CUphasecable0.861717[Degrees/km]
Phase shift(50Hz) ALphasecable1.363[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.555[mA]




Core figure f
Cable-InductanceLcable0.892[mH/km]
Cable-ReactanceXcable280.113[mΩ/km]
Cable-CapacitanceCcable58.563[nF/km]
Cable-Impedance(50Hz) CUZcable2985.69[mΩ/km]
Cable-Impedance(50Hz) ALZcable4711.224[mΩ/km]
Voltage drop(50Hz) CUVcable2.986[V/km]
Voltage drop(50Hz) ALVcable4.711[V/km]
Phase shift(50Hz) CUphasecable0.607992[Degrees/km]
Phase shift(50Hz) ALphasecable0.962[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.423[mA]




Core figure g
Cable-InductanceLcable0.446[mH/km]
Cable-ReactanceXcable140.057[mΩ/km]
Cable-CapacitanceCcable117.255[nF/km]
Cable-Impedance(50Hz) CUZcable2975.819[mΩ/km]
Cable-Impedance(50Hz) ALZcable4704.975[mΩ/km]
Voltage drop(50Hz) CUVcable2.976[V/km]
Voltage drop(50Hz) ALVcable4.705[V/km]
Phase shift(50Hz) CUphasecable1.215846[Degrees/km]
Phase shift(50Hz) ALphasecable1.923[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.847[mA]




Core figure h
Cable-InductanceLcable0.629[mH/km]
Cable-ReactanceXcable197.629[mΩ/km]
Cable-CapacitanceCcable76.821[nF/km]
Cable-Impedance(50Hz) CUZcable2979.084[mΩ/km]
Cable-Impedance(50Hz) ALZcable4707.04[mΩ/km]
Voltage drop(50Hz) CUVcable2.979[V/km]
Voltage drop(50Hz) ALVcable4.707[V/km]
Phase shift(50Hz) CUphasecable0.861717[Degrees/km]
Phase shift(50Hz) ALphasecable1.363[Degrees/km]
Power loss(per conductor) CUPcore2.973[Watt/km]
Power loss(per conductor) ALPcore4.703[Watt/km]
Capacitive loading current [V=230, cable length=100meter]Icap0.555[mA]
© 2021 CASPOC, All rights reserved. Home   |   Terms and Conditions   |   Legal   |   Export Compliance   |   Privacy Policy   |   Site Map